Alarmcodes Yaskawa Varispeed 626

Alarm Codes (Alarm-Codes) und Fehlermeldungen für die Yaskawa Varispeed VS-626M5 und VS-656MR5 Serie.

Bitte nutzt die Kommentarfunktion, wenn Ihr weitere Hilfestellung zur Fehlerbehebung geben könnt.

Items 88

Fault No. Name Contents Corrective Actions Comments
88888 YENET1200 communication signal delay After turning control power ON, NC machine and YENET1200 communication is not establishe

- Check the wiring of YENET1200 communicatin line
- Check NC machine power supply

AL-01 Overcurrent Output current exceeded overcurrent detection value, or Inverter output (load) was short-circuited Check the wiring for Looseness, etc
AL-02 Ground fault Inverter output side ground current exceeded grounding detection level

- Check the motor for deteriaration of insulation
- Check the wiring between Inverter and motor

AL-04 Main circuit fuse blown DC circuit fuse was blown

- Check for damage to transinstor, short-circuits on laod side, ground fault, etc.
- Check the Inverter output wiring

AL-05 Inverter output overload Output current of 120% of 30-minute ratin runs for over one minute

- Reduce the load
- Check the load shaft (Inverter, Servo) capacity

AL-06 Motor overload Motor overload capacitiy exceeded Reduce the load
AL-07 Motor Overload (When the motor is locked) The motor exceede the overload level at low speed (30 min-1 or less)

- Check if the load is heavy or a tool is jammed
- Make sure that the motor shaft rotates. (Check if a motor fault or a contact between the rotor and the stator occurs, of if a bearing is damaged.)

AL-10 Converter fault A fault occurred in Converter Unit. Check fault contens by using Converter LED
AL-11 Main ciruit overvoltage Main circuit DC bus voltage exceeded the overvoltage set value.

- Check the input supply voltage
- Check the load shaft (Inverter, Servo) capacity
- Check the control constants

AL-12 Main circuit undervoltage Main circuit DC bus voltage bacame lower than undervoltage detection level during run. Check the input supply voltage.
AL-13 Control circuit undervoltage Control cirguit power supply became lower then undervoltage detection level Check the control supply voltage
AL-20 Winding selection fault Winding selection was not completed within set time

- Check the control constant C1-25
- Check the manetic contactor wiring for winding selection

AL-21 Emergency stop fault Inverter did not stop within 10 seconds after emergency stop command

- Check control constant C1-25
- Check the setting of control constant C1-24 and wether external torque limit signals TLL and TLH are input

AL-30 Encoder signal cable disconnection Motor encoder signal was disconnected or connected improperly Check the wiring of encoder signal lines
AL-31 Motor overspeed Motor speed exceeded 120% of set rated speed

- Confirm that encoder signal lines are separated from main circuit or other power lines
- Check the control constants

AL-32 Excessive seed deviation Seed falls to less than 50% of reference value

- Check if the load is heavy or a tool is jammed
- Check whether external torque limit signals TLL and TLH are input
- Check the control constants
- Check the wiring of encoder signals lines

AL-33 Motor Lock Detection (For IP motors only) The motor is locked. (The motor speed remains at 35 min-1 or lower for 10 seconds during the toque refernece saturation.)

- Check if the load ist heavy or al tool is jammed
- Check the wiring between Inverter and motor
- Check the wiring of encoder singal lines
- Make sure that the motor shaft rotates
- Check if a motor fault or a conact between rotor an stator occurs, or if a bear is damaged

AL-40 Motor overheat 1 Motor temperatur exceeded upper limit (minor fault)

- Check the wiring
- Confirm that motor colling air is normal with power ON
- Confirm that the fan is not clogged with dust or oil
- Check the wiring of motor thermistor signal lines
Notice:
NTC value is about 10 kOhms at 25 C Celsius

AL-41 Motor overheat 2 Motor temperatur over upper limit continued for over one minute

- Check the wiring
- Confirm that motor colling air is normal with power ON
- Confirm that the fan is not clogged with dust or oil
- Check the wiring of motor thermistor signal lines
Notice:
NTC value is about 10 kOhms at 25 C Celsius

AL-42 Motor thermistor disconnection Motor temperature detection thermistor was disconnected

- Check the motor thermistor singal wiring
- Check the motor ambient temperatur. (Raise the temperature to above - 10 °C or more.)

AL-43 Heatsink overheat 1 Heatsink temperature exceeded uper limit (minor fault). Check the ambient temperature for effective cooling
AL-44 Heatsink overheat 2 Heatsink temperature over upper limit continued for one minute or longer Check the ambient temperature for effective cooling
AL-45 Heatsink thermistor disconnection

Thermistor for heatsink temperature detection was disconnected.
The ambient temperature is low (< - 20°C).

- Replace the unit
- Raise the ambient temperature to above -20°C

AL-46 Control PCB temperature fault 1 Control PCB temperature exceeded 80°C Check the ambient temperature for effective cooling
AL-47 Control PCB temperature fault 2 Control PCB temperature exceeded 85°C Check the ambient temperature for effective cooling